Exposed wash basin tap VITUS VW-C-T
Exposed wash basin tap VITUS VW-SC-M
Exposed wash basin tap VITUS VW-E-T
Mixed water, ThermoProtect thermostat
Mixed water
Mixed water, ThermoProtect thermostat
Article number
Triggering via CVD-Touch electronics with automatic closing. Battery operation. With integrated SWS BE-F VITUS wireless bus extender for networking with the SWS water management system.
Manual actuation with automatic closing. Easy flow time adjustment.
Infrared sensor-controlled. Battery operation. Suitable for networking with the SCHELL SWS water management system. Configurable via SCHELL Single Control SSC.

Scope of delivery

  • Electronic self-closing exposed wash basin tap
    • ThermoProtect thermostat, conform to EN 1111, unlockable/lockable temperature lock at 38 °C, anti-scalding protection if cold water supply fails
    • CVD-Touch electronics, programmable, IP65 protection against low-pressure water jets
    • SWS BE-F VITUS wireless bus extender
    • Solenoid valve 6 V automatic thermal disinfection with SWS (in accordance with DVGW worksheet W 551).
    • 6 V solenoid valve with pre-filter
    • 2 backflow preventers (EN 1717: EB-type)
    • Pivoting outlet (lockable) with flow regulator
    • 6 V battery compartment (integrated)
  • 4x AA alkaline battery 1.5 V
  • 2 S-connections and rosettes (depth-adjustable)

Delivery data

  • Weight: 5,32 kg/Piece
  • Packing unit: 1

Scope of delivery

  • Self-closing exposed wash basin tap
    • SC-M self-closing button
    • Valve (mechanical) for thermal disinfection (according to DVGW worksheet W 551)
    • Self-closing cartridge SC II with hot water restrictor
    • 2 backflow preventers (EN 1717: EB-type)
    • Pivoting outlet (lockable) with flow regulator
  • 2 S-connections and rosettes (depth-adjustable)

Delivery data

  • Weight: 4,82 kg/Piece
  • Packing unit: 1

Scope of delivery

  • Infrared sensor exposed wash basin tap
    • ThermoProtect thermostat, conform to EN 1111, unlockable/lockable temperature lock at 38 °C, anti-scalding protection if cold water supply fails
    • Infrared sensor electronics, programmable
    • 6 V solenoid valve with pre-filter
    • 2 backflow preventers (EN 1717: EB-type)
    • Pivoting outlet (lockable) with flow regulator
    • 6 V battery compartment (integrated)
  • 2 S-connections and rosettes (depth-adjustable)

Delivery data

  • Weight: 5,08 kg/Piece
  • Packing unit: 1

Technical data

  • Setting options via SWS SSC
    • Actuation force (soft/medium/hard)
    • Manual programming (off/on)
    • Max. flow time (1-950 s)
    • Stagnation flush (off/1-1000 s, every 1-250 h after last flush/every 1-250 h)
    • Actuation timeout (off/1-255 s, timeout 1-2000 min)
  • Setting options via manual programming
    • Max. flow time (4-120 s, 10 program stages)
    • Stagnation flush (off/20 s, every 24 h)
  • Flow: max. 5 l/min pressure independent
  • Flow pressure: 1.0 - 5.0 bar
  • Max. Resting pressure: 8 bar
  • Max. operating temperature: 70 °C (80 °C for thermal disinfection)
  • Material: Outlet Brass, conform to German drinking water regulations; Housing Brass, conform to German drinking water regulations
  • Surface: Chrome
  • Projection to centre of aerator: 270 mm
  • Connection: 2x DN 15 G 1/2 AG
  • Certificates: PA-IX 28575/IO, Belgaqua
  • Noise class: I
  • Flow class: O

Technical data

  • Running time: 2 - 15 s (7 s )
  • Flow: max. 5 l/min pressure independent
  • Flow pressure: 1.0 - 5.0 bar
  • Max. operating temperature: 70 °C (80 °C for thermal disinfection)
  • Material: Outlet Brass, conform to German drinking water regulations; Housing Brass, conform to German drinking water regulations
  • Surface: Chrome
  • Projection to centre of aerator: 270 mm
  • Connection: 2x DN 15 G 1/2 AG
  • Certificates: PA-IX 38237/IO, Belgaqua
  • Noise class: I
  • Flow class: O

Technical data

  • Setting options via SWS SSC
    • Programming via short range reflex (off/on)
    • Max. flow time (1-600 s)
    • Stagnation flush (off/5-600 s, every 1-240 h after last flush/every 1-240 h)
    • Continuous flush for thermal disinfection (off/15-600 s)
    • Duration of flow (off/15-600 s)
    • Energy saving mode (off/1-254 h after last flush)
    • Cleaning stop (off/60-360 s)
  • Setting options via short range reflex
    • Max. flow time (4-240 s, 12 program stages)
    • Stagnation flush (off/30 s, every 24 h after last flush/every 24 h)
    • Cleaning stop (off/60 s)
  • Flow: max. 5 l/min pressure independent
  • Flow pressure: 1.0 - 5.0 bar
  • Max. Resting pressure: 8 bar
  • Max. operating temperature: 70 °C (80 °C for thermal disinfection)
  • Material: Outlet Brass, conform to German drinking water regulations; Housing Brass, conform to German drinking water regulations
  • Surface: Chrome
  • Projection to centre of aerator: 210 mm
  • Connection: 2x DN 15 G 1/2 AG
  • Certificates: PA-IX 38235/IO, Belgaqua, WRAS applied
  • Noise class: I
  • Flow class: O
Filter categories
System solutions
SWS Water Management System,
Single Control SSC
-
SWS Water Management System,
Single Control SSC
Connection
1/2"
-
-
Function
Self-closing electronic
Self-closing mechanical
Contact-free,
Self-closing electronic
Temperature
Thermostat (incl. scald protection)
Mixed water
Thermostat (incl. scald protection),
Mixed water
Watersaving
Start/stop function
-
-
Hygiene
Stagnation flush,
Therm. disinfection
Therm. disinfection
Stagnation flush
Energy supply
Battery mode
-
Battery mode
Finish
Chrome
Chrome
Chrome
Pressure
High pressure / standard pressure
-
High pressure / standard pressure
Equipment
Backflow preventer
-
Backflow preventer,
Flow restrictor
3